A catalog download is here.
SA200_03E.pdf (268KB)
Specification files are in Adobe's Acrobat PDF file (version 4.0)
format. Acrobat Reader is required. |
| Input |
Thermocouple, RTD, DC voltage, DC current
* For DC current input, connect a 250W resister (sold separately) to the input terminals. |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
Thermocouple
±(0.3% of reading + 1 digit) or ±2°C (4°F) whichever is larger
RTD
±(0.3% of reading + 1 digit) or ±0.8°C (1.6°F) whichever is larger
DC voltage and DC current
±(0.3% of span + 1 digit)
|
| Out of an accuracy guarantee range |
Thermocouple R, S, B : 0 to 399°C
Thermocouple T, U : Less than -100°C |
| Control method |
PID control (with autotuning and self-tuning function)
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control (with autotuning) |
| Control output type |
Relay contact output
Voltage pulse output |
| Communications |
@RS-485 |
| External Dimensions |
48 x 24 x 100mm (W x H x D) |
| Standard function |
RUN/STOP switching |
| Optional function |
Alarm function : Up to 2 points (Temperature alarm, Loop break alarm)
Contact input : 2 points
Dustproof and waterproof protection : IP66 |
|