A catalog download is here.
SRV_01E.pdf (345KB)
Specification files are in Adobe's Acrobat PDF file (version 4.0) format.
Acrobat Reader is required. |
| Configuration |
A maximum of 31 modules can be connected for 62-loop control.
Dual loop control can be performed with a single compact module. |
| Input |
Thermocouple, RTD, DC voltage, DC current |
| Sampling time |
0.5 sec. |
| Measuring accuracy |
Thermocouple : K, J, T, E, PLII
Less than -100°C : ± 2.0°C
-100 to 333°C : ± 1.0°C
More than 334°C : ±( 0.3% of reading + 1 digit )
Thermocouple : N, S, R, W5Re/W26Re
Less than 666°C : ± 2.0°C
More than 667°C : ±( 0.3% of reading + 1 digit )
Thermocouple : B
Less than 400°C : ± 70.0°C
400 to 666°C : ± 2.0°C
More than 667°C : ±( 0.3% of reading + 1 digit )
RTD
Less than 266°C : ± 0.8°C
More than 267°C : ±( 0.3% of reading + 1 digit )
DC voltage and DC current
±(0.3% of span) |
| Control method |
Brilliant PID control ( ON/OFF control, PI control is selectable. )
( with enhanced autotuning )
Heat/cool brilliant PID control
( with autotuning ) |
| Control output type |
Relay contact output
Voltage pulse output
DC current output
DC voltage output |
| Communications |
RS-485
MODBUS supported. |
| Type of module |
Temperature Control Module ( with heater break alarm ) |
|