| Storage program pattern |
Max. 16 patterns
16 segments per pattern
( Max. 256 segments when linking 16 patterns of 16 segments each. ) |
| Input |
Universal input Thermocouple, RTD, DC voltage, DC current |
| Sampling time |
0.1 sec. |
| Measuring accuracy |
Thermocouple
(±0.1% of reading or ±1°C) ± 1digit
RTD
(±0.1% of reading or ±0.5°C) ± 1digit
DC voltage and DC current
±(0.1% of span + 1 digit) |
| Out of an accuracy guarantee range |
Thermocouple B, PR20-40 : Less than 400°C
RTD JPt100 : More than 500°C |
| Cold junction temperature compensation error |
Within ±0.5°C ( between 0 and 50°C )
But input value does not guarantee less than -100 °C. |
| Control method |
PID control ( with autotuning )
* ON/OFF, P, PI and PD control are also selectable.
Heat/cool PID control ( with autotuning )
Position proportioning control without feedback resistance |
| Control output type |
Relay contact output
Voltage pulse output
DC current output
DC voltage output |
| Communications |
RS-232C
RS-422A
RS-485 |
| External Dimensions |
96 x 96 x 100mm ( W x H x D ) |
| Standard function |
Programmable ramp/sork control
Level PID control (4 level)
Pattern end output : 1 point ( Open collector )
Time signal output : 4 points ( Open collector )
External contact input : 4 points
( RESET, RUN, HOLD, STEP )
Alarm function : Max. 2 points |
| Optional function |
Time signal output : In the case of 8 points.
Auxiliary output : Max. 3 points
External contact input : 5 points ( Pattern set ) Analog retransmission output |