Compliance
 |
RoHS compliant |
|
 |
CE Marking |
|
 |
UL, cUL |
|
 |
C-Tick Mark |
Specifications
| Input |
Universal input
a) Temperature, current, voltage (low) input group
- Thermocouple input : K, J, E, T, R, S, B, N, PLII, W5Re/W26Re, U, L, PR40-20
- RTD : Pt100, JPt100 (3-wire type)
- DC Voltage input (input impedance: 1MW) : 0 to 1V, 0 to 100mV, 0 to 10mV, -100 to +100mV,
-10 to +10mV, -1 to +1V
b) Voltage (high) input group
- DC Voltage input (input impedance: 1MW) : 0 to 5V, 1 to 5V, 0 to 10V, -5 to +5V, -10 to +10V
c) Current input group
- DC Current input (input impedance: 50W) : 4 to 20mA, 0 to 20mA
(Use dip switch to change input group.) |
| Sampling time |
0.1 sec (0.05sec/0.25sec is selectable.) |
Measuring
accuracy |
Thermocouple Type : K, J, T, E, PLII, U, L
- Less than -100°C (-148°F) : ±1.0°C (±1.8°F)
- -100 to +500°C (-148 to 932°F) : ±0.5°C (±0.9°F)
- More than 500°C (932°F) : ±0.1% of reading
Thermocouple Type : N, S, R, W5Re/W26Re
- Less than 0°C (32°F) : ±2.0°C (±3.6°F)
- 0 to 1000°C (32 to 1832°F) : ±1.0°C (±1.8°F)
- More than 1000°C (1832°F) : ±0.1% of reading
Thermocouple Type B
- Less than 400°C (752°F) : ±70.0°C (±126°F)
- 400 to 1000°C (752 to 1832°F) : ±1.4°C (±2.6°F)
- More than 1000°C (1832°F) : ±0.1% of reading
Thermocouple Type PR40-20
- Less than 400°C (752°F) : ±20°C (36°F)
- 400 to 1000°C (752 to 1832°F) : ±10°C (18°F)
- More than 1000°C (1832°F): ±0.1% of displayed value
RTD
- Less than 200°C (392°F) : ±0.2°C (±0.4°F)
- More than 200°C (392°F) : ±0.1% of reading
DC voltage and DC current
|
Cold junction
temperature
compensation error
|
±1.0°C (1.8°F) [Between 5 and 40°C (41 and 104°F)]
±1.5°C (2.7°F) [Between -10 and 5°C (16 and 41°F), and 40 and 55°C (104 and 122°F)] |
| Control method |
a) Brilliant II PID control
- Direct action/Reverse action is selectable
b) Brilliant II PID control (Heat/Cool type)
c) Brilliant II position proportioning control
- Direct action/Reverse action is selectable
- Position proportional control can be used with/without FBR (feedback resistance) input.
・a), b), c) selectable |
| Program control |
| Time accuracy |
±0.01% of reading or input sampling time, whichever is larger. |
Number of
program patterns
|
Up to 99 patterns |
Number of
program segments |
Up to 1024 segments
・Up to 99 segments per pattern.
・Supplied with hold, step, fast forward, fast rewind features. |
| Segment time |
0 hr 0 min to 500 hs 00 min or 0 min 0 sec to 500 min 0 sec |
Number of
segment repeat |
1 to 9999 repeats
・ Repeat is disabled when set to 1. |
Number of
pattern repeat |
1 to 9999 repeats
・Continuous repeat when set to 10,000. |
Number of
linkable patterns |
0 to 99 patterns
・No pattern link when set to zero |
Pattern end
output time |
0 hr 0 min to 500 hs 00 min or 0 min 0 sec to 500 min 0 sec
・Output remains on when set to zero. |
Time signal memory
group number |
0 to 16
・No assigned groups when set to zero. |
Program starting
mode |
a) Starts from a desired value (SV after reset)
b) Starts from a desired measured input (Time fixed)
c) Starts from a desired measured input (Time shortened)
d) Intersection of measurement input and pattern is searched
and starts from there. (HOLD status when started)
e) Intersection of measurement input and pattern is searched
and starts from there. (RUN status when started) |
WAIT status at the
time of program start |
WAIT condition memory number : 0~8
・No WAIT when set to zero.
・Selectable from release by wait zone, contact input (trigger), and timeout. |
| WAIT function |
a) Wait zone (upper)
- 1) Temperature input: 0 (0.0/0.00) to 200 (200.0/200.00)(°C,°F)
- 2) Voltage/current input: 0.0 to 20.0% of input span
- ・Wait function off when set to zero
b) Wait zone (lower)
- 1) Temperature input: -200(-200.0) to 0(0.0)(°C,°F) or -199.99
to 0.00(°C,°F)
- 2) Voltage/current input: 20.0 to 0.0% of input span
- ・Wait function off when set to zero
c) Wait timeout
(Time counting resumes unconditionally after the set time has elapsed)
- 0 hr 0 min to 500 hs 00 min or 0 min 0 sec to 500 min 0 sec
- ・Function is disabled when set to zero.
|
| Pattern end output |
・DO can be assigned (turns on for 0.5 second for each pattern repeat). |
| Time signal output |
Time signal or segment signal, whichever is specified.
a) Time signal
- 1) Number of outputs: 8 (TS1 to TS8)
- 2) Output assignment: Up to 12 (including 4 relays), assignable by DO
- 3) Time signal memory group: 16 groups
- 4) Number of memory storage: 16 groups X 16 memories
- 5) Number of storage memory: 1 to segment No. (max = 99)
- 6) Starting time: 0 hr 0 min to 500 hs 00 min or 0 min 0 sec to
500 min 0 sec
- 7) Ending segment: 1 to segment No. (max = 99), however, ending
segment must be equal to or larger than the starting segment.
- 8) Ending time: 0 hr 0 min to 500 hs 00 min or 0 min 0 sec to
500 min 0 sec
b) Segment signal: TS1 to TS8 can be independently turned ON and OFF at
each segment. |
Programmed
preset manual
output
(Output program
function) |
Fixed value is produced at each segment.
The function is activated by assigning outputs 1 to 3 to the program output.
a) Number of output program patterns: 1 to (128/max. segments number)
For example, in case of 99 segments, it is "1".
- ・Max. segment No.: Number of segments by number of patterns multiplied
by number of segments.
b) Setting items: Output program 1 to 3 : -5.0 to +105.0%
(Independently adjustable). |
| Other features |
Pattern/segment copy function, tag name edit function (for each pattern), data clear (to initial state), remaining time display of pattern. |
|
| Control output |
a) Relay contact output : Form 1a contact, Rating: 250V AC 3A (Resistive
load)
- Electrical life: 300,000 cycles or more
b) Voltage pulse output : 0/12V DC, Load resistance : 600W or more (20mA or less)
- * OUT1 can be 300W or more (40mA or less) if OUT2 is not used.
c) Current output : 4 to 20mA, 0 to 20mA DC, Load resistance: 600W or less
d) Continuous voltage output : 0 to 5V, 1 to 5V, 0 to 10V, 0 to 1V DC
(Assignable to OUT3 only), Load resistance: 1KW or more
e) SSR output (triac output) : current rating 0.5A
f) Open collector output (sink method) : Load voltage 30V DC or lower
- Allowable load current: 100mA.
- ON voltage: 2V or less (For maximum load current)
|
Communication
(Optional) |
RS-485/RS-422A/RS-232C
(To be specified at the time of ordering) |
Inter-controller
communication
(Optional) |
Function to send target value to slave controllers.
RS-485 (Protocol : MODBUS-RTU)
Maximum slaves : 4 units |
Loader
communication |
Protocol : RKC standard (ANSI X3.28 subcategory 2.5 A4)
Front: Connected to COM-K with an exclusive cable (W-BV-03-1500)
· Front loader interface is available only while instrument is powered. |
Standard
function |
· PV bias
· PV ratio
· Digital filter
· Square root extraction
PV = √(Input value) x PV ratio + PV bias
Low level cut off : 0.00 to 25.00% of span
· Event (alarm) function : Up to 4 points (event 1 to 4)
· Loop break alarm (LBA)
(Loop break alarm (LBA) is not available for heat/cool PID control type.)
· Digital input (DI): DI7 to DI11: Standard (DI1 to DI6: Optional)
· Digital output (DO): OUT2, DO1 to DO4: Standard (OUT3, DO5 to
DO12: Optional) |
Optonal
function |
· Heater break alarm (HBA)
(Heater break alarm (HBA) is not available for current/continuous voltage
output.)
· Retransmission output (AO)
· Digital input (DI): DI1 to DI6: Optional (DI7 to DI11: Standard)
· Digital output (DO): OUT3, DO5 to DO12: Optional (OUT2, DO1 to
DO4: Standard) |
Dimensions
| Units : mm) |
![Dimensions : Ramp/Sork Controller [Process/Temperature Controller] PF900](images/pf900_exte.gif) |
Model and Suffix Code
<Note 1>
If inter-controller communication (master-slave operation) is used, select
code: W, X, or Y (that means "with communication 2") for a master
device, and 5 or X (communication 1: RS-485) for a slave device. |
| *1 |
For program or retransmission output, specify voltage or current.
For digital output, specify relay or open collector output. |
| *2 |
Heater break alarm (HBA) is not available or current/continuous voltage output.
Loop break alarm (LBA) is not available for heat/cool PID control type. |
| *3 |
Position proportional control can be used with/without FBR (feedback resistance)
input. |
Control output (OUT1, OUT2) assignment by control action
PID control action:
Control output is produced from OUT1. OUT2 can be used as retransmission
output or digital output.
Heat/Cool PID control action:
Heating output is produced from OUT1 and cooling output from OUT2.
Position proportioning PID control action: Opening output is produced from OUT1 and closing output from OUT2. |
Quick start code 2
|